Insulation Piercing Clamp

Product Details
Customization: Available
Transport Package: Carton
Specification: 35*35*30
Still deciding? Get samples of US$ 0.5/Piece
Request Sample
Manufacturer/Factory, Trading Company
Gold Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO 9001
  • Insulation Piercing Clamp
  • Insulation Piercing Clamp
  • Insulation Piercing Clamp
  • Insulation Piercing Clamp
  • Insulation Piercing Clamp
  • Insulation Piercing Clamp
Find Similar Products

Basic Info.

Model NO.
JMAEP
Trademark
JMA
Origin
China
HS Code
8538900000
Production Capacity
100000000000PCS

Product Description

DRAWING
Insulation Piercing ClampInsulation Piercing ClampInsulation Piercing ClampInsulation Piercing ClampInsulation Piercing Clamp
Description: The insulation piercing connectors are applicable for all types of LV-ABC conductors as well as connections in service line system, building electrical system and street lighting system. Insulation piercing connectors can be easily done by tightening the bolts to force the teeth penetrate the insulation of main line and tap line simultaneously. Stripping of insulation is avoided for both lines.
Main line: Insulated aluminium cable
Tap line: Insulated aluminium cable or Insulated copper cable
Body is moulded from tough and weather resistant materials
Special designed shear head bolt allows efficient installation under controlled shear torque which ensure the contact teeth properly penetrate the conductor without damaging the mechanical strength of the conductor
Tested for watertightness at the voltage of 6kV for 1min under water
Safe live-line installation
Seals and grease are applied to prevent moisture entering the cable and connector which guarantees excellent waterproof and corrosion resistant performance
End cap is attached to the body. No loose parts could fall to ground during installation 
Standard: EN 50483-4, NFC 33-020, NFC 33-004  
Technical specification

Dimensions

Main Cable Line:

1.5-2.5mm²

Branch Cable Line:

1.5-10mm²

Norminal Current:

75A

Piercing Depth:

1-2mm

Features

Bolt:

M6*55

Mechnical

Tightening Torque:

10Nm

 